GenetixBayEST. 2009
Equipment · Intermediate · 6 min read

Calculate it properly: AC and cooling load for a grow tent or room

Your cooling load is every watt you plug in, times 3.412 BTU/h, plus heat through walls and from people. Lights, drivers, fans, pumps and the dehumidifier all count. Plants don't add heat; they turn some of it into humidity, and a dehumidifier turns it back into heat. A sealed 10×10 ft room with about 3,300 W of LED needs roughly 16,000 BTU/h (1.3 tons) of cooling with dehumidification, before a 10–20% margin. Prefer a mini-split to a single-hose portable unit.

Supported
Draft: awaiting expert review Updated
Any stageAny system

Being reviewed. Our editors are double-checking a figure in this article against primary sources. Marked passages may change.

Short answer, in plain words. Everything you plug in turns into heat, so your cooling job is simple to add up: every watt × 3.412 = BTU per hour. Add the lights, the drivers, the fans, the pumps and the dehumidifier. Add a little for hot walls and for you when you're in there. Divide by 12,000 to get tons. A sealed 10 × 10 ft room with about 3,300 W of top-tier LED comes to roughly 16,000 BTU/h (1.3 tons), then add 10–20% margin. Plants don't add heat; they hide some of it as humidity, and the dehumidifier hands it back. Established (physics); example values are labelled assumptions.

Use the calculator: AC and cooling calculator. Planning the whole tent at once: whole-tent planner.

What is the formula?

Total cooling load (BTU/h) = sensible gains + latent gains, and in a grow room nearly all of it is electrical:

  • Every device: watts × 3.412 = BTU/h [1][2]. Lights (measured at the wall, so drivers and ballasts are included), fans, pumps, controllers, chillers, and the dehumidifier's own watts.
  • People: about 450 BTU/h each while inside (about 250 sensible and 200 latent, for moderately active work) [2].
  • Walls and ceiling: BTU/h ≈ area (ft²) × temperature difference (°F) ÷ R-value. In metric: W ≈ area (m²) × temperature difference (K) ÷ RSI.
  • Tons = BTU/h ÷ 12,000. kW = BTU/h ÷ 3,412 [1].

What about the plants? They don't add energy. When leaves transpire, they turn some of the room's heat (mostly from the lights) into water vapour: about 2,450 kJ per kg of water, or roughly 2,320 BTU per litre (1,050 BTU/lb) [3]. That's a latent load: humidity instead of temperature. The total stays the same; only the split between "hot" and "humid" changes.

Why a dehumidifier adds heat. A dehumidifier adds all its electrical watts as heat, and when it condenses the water it releases that latent heat back into the room as sensible heat, about 2,320 BTU per litre [3]. So with the dehumidifier doing the drying, your AC must remove: all the electrical watts (dehumidifier included) as plain heat.

The orderAdding up a cooling load
  1. List every deviceLights, fans, pumps, dehumidifier
  2. × 3.412BTU/h
    • walls and people
    ~450 BTU/h per person
  3. ÷ 12tons
    • 10–20% margin

Source: [1][2]

Worked example: a sealed 10 × 10 ft room

Assumptions (labelled; change them to your own): flower at about 900 µmol/m²/s with a top-tier 3.0 µmol/J LED (about 3,280 W, see lighting sizing); 300 W of circulation fans, controllers and a pump; plants using about 37 L (9.8 US gal) of water a day, about 90% of it in the 12-hour lights-on period (see dehumidifier sizing); a dehumidifier removing that at about 2.8 L/kWh, so about 1,000 W while the lights are on; an interior room with modest wall gains.

Item Watts BTU/h
LED lights (wall watts) 3,280 11,190
Fans, controllers, pump 300 1,020
Dehumidifier (electrical) 1,000 3,410
Walls and ceiling (interior room; assumption) ~300
One person, while inside ~450
Total ~16,370 (1.36 tons)
With 15% margin ~18,800 (1.57 tons)

The transpired water (about 2.8 L/h in lights-on, about 6,500 BTU/h of latent heat) isn't a separate line: it came out of the light's heat and goes back in when the dehumidifier condenses it [3].

ChartWhere the heat comes from in a sealed 10 × 10 roomIn the worked example the LED lights add about 11,190 BTU/h, the dehumidifier about 3,410, fans and controllers about 1,020, and walls plus one person about 750: about 16,370 BTU/h, or 1.36 tons.
  • LED lights
  • Dehumidifier
  • Fans, controllers, pump
  • Walls and one person
06,00012,00018,000Heat load (BTU/h)Sealed 10 × 10 roomSealed 10 × 10 room, LED lights: 11,190 BTU/h11,190Sealed 10 × 10 room, Dehumidifier: 3,410 BTU/h3,410Sealed 10 × 10 room, Fans, controllers, pump: 1,020 BTU/hSealed 10 × 10 room, Walls and one person: 750 BTU/h16,37006,00012,00018,000Heat load (BTU/h)Sealed 10 × 10 roomSealed 10 × 10 room, LED lights: 11,190 BTU/h11,190Sealed 10 × 10 room, Dehumidifier: 3,410 BTU/h3,410Sealed 10 × 10 room, Fans, controllers, pump: 1,020 BTU/hSealed 10 × 10 room, Walls and one person: 750 BTU/h16,370

Source: Worked example table above; watts × 3.412 [1]; people [2].

Show the numbers
RoomLED lights (BTU/h)Dehumidifier (BTU/h)Fans, controllers, pump (BTU/h)Walls and one person (BTU/h)Total (BTU/h)
Sealed 10 × 10 room11,1903,4101,02075016,370
By the numbersSealed 10 × 10 room, worked example
  • ~16,370 BTU/hTotal heat load
  • 1.36 tonsBefore margin
  • 1.57 tonsWith 15% margin
  • ~6,500 BTU/hLatent share the AC alone would struggle with

Source: Worked example above [1][2][3].

What if the AC does the drying instead? Without a dehumidifier the total is smaller (about 12,960 BTU/h including walls and one person), but about half of it is latent. Most comfort air conditioners are built to remove only about a fifth to a third of their capacity as moisture (check the unit's published sensible and latent capacity)being reviewed. So in flower the AC alone can't keep RH down. That's why sealed rooms pair an AC with a dehumidifier, or use equipment built for high latent loads.

Choosing the unit: at about 1.6 tons with margin, an 18,000 BTU/h (1.5-ton) variable-speed unit is close; a 24,000 BTU/h (2-ton) unit gives headroom but risks short-cycling at lights-off unless it is inverter-driven. Grower practice.

How much cooling for each tent size?

Same assumptions per square foot: top-tier LED at about 900 µmol/m²/s, fans scaled to size, plants using about 4 L/m²/day, a dehumidifier at 2.8 L/kWh. These are the heat each space adds to the room it sits in.

Space Lights (W) Fans etc. (W) Dehumidifier (W, lights-on) Total heat (BTU/h) Tons
2 × 4 ft tent ~260 40 ~80 ~1,310 0.11
4 × 4 ft tent ~525 80 ~160 ~2,610 0.22
5 × 5 ft tent ~820 100 ~250 ~4,000 0.33
4 × 8 ft tent ~1,050 120 ~320 ~5,090 0.42
10 × 10 ft room ~3,280 300 ~1,000 ~15,650 1.30

Add people, wall gains and a 10–20% margin. With double-ended HPS at 1.7 µmol/J for the same light, the lights alone need about 1.75 times the watts, so the load climbs accordingly (see LED vs HPS: the heat and power-bill myth).

Tents inside a house. A tent exhausting into the room it sits in hands all its heat to that room, so the house AC must remove it. A tent exhausting outdoors removes its heat, but the house must replace the air it throws out, and that make-up air brings outdoor heat and humidity in. Established (energy balance).

How much do walls and ceilings add?

Usually little for an interior room, a lot for an attic, garage or exterior wall. Gain ≈ area × ΔT ÷ R [2].

  • Interior wall, 80 ft², R-4 (uninsulated drywall), 5 °F warmer outside the room: 80 × 5 ÷ 4 = 100 BTU/h.
  • Ceiling under a hot attic, 100 ft², R-30, attic 120 °F vs room 78 °F (ΔT 42 °F): 100 × 42 ÷ 30 = 140 BTU/h. Uninsulated (about R-3): 1,400 BTU/h.
  • Exterior wall in sun, 80 ft², R-13, ΔT 20 °F: 125 BTU/h; uninsulated: about 530 BTU/h.

Metric: W = m² × K ÷ RSI (RSI = R ÷ 5.678).

Mini-split or portable AC?

For a sealed room, a ductless mini-split. Avoid single-hose portable units. Supported.

  • Single-hose portable: it blows room air across its hot condenser and out the window. That creates negative pressure, and the same volume of warm, unconditioned air leaks back in through every gap. US Department of Energy test rules now count this infiltration, which is why newer labels show a lower "seasonally adjusted" capacity than older ones [5]. In a sealed CO₂ room it also throws out your CO₂.
  • Dual-hose portable: pulls condenser air from outside and returns it outside, so it avoids most of the infiltration problem. Better, still noisy and less efficient than a split.
  • Mini-split: the hot condenser is outdoors; the indoor head only moves room air, so it doesn't depressurise the room or dump CO₂. Variable-speed models handle lights-on/lights-off swings well. Refrigerant work needs a certified technician (EPA Section 608 in the US) [6]; check local permit rules.
  • Window unit: fine for some rooms; it vents like a dual-hose but needs a window and leaks some air around its seals.

Don't oversize much. A unit far bigger than the load cools fast, shuts off, and removes less moisture, so humidity rises [4]. Size for the load plus 10–20%.

Common mistakes

  • Counting only the lights. Fans, pumps, dehumidifiers, chillers and controllers all add 3.412 BTU/h per watt [1][2].
  • Forgetting the dehumidifier's heat, or sizing the AC with the dehumidifier off.
  • Adding plant transpiration as extra heat. It's the light's heat, changed into humidity; count it when choosing how to dry the air, not as extra cooling load.
  • Using lamp-rated watts instead of measured wall watts.
  • Buying a single-hose portable for a sealed room and wondering why it's hot and the CO₂ is gone [5].
  • Massively oversizing and fighting high RH in flower [4].
  • Ignoring lights-off. The load drops by the lights' share; a single-speed unit may short-cycle and humidity can spike (see dehumidifier sizing).

Questions this article answers

How many BTU do I need to cool my grow room?

Add up every watt running in the room (lights, drivers, fans, pumps, dehumidifier, controllers) and multiply by 3.412 to get BTU/h, then add wall and ceiling gains and about 450 BTU/h per person while you're inside. A sealed 10×10 ft room with about 3,300 W of LED, 300 W of fans and a 1,000 W dehumidifier comes to about 16,000 BTU/h, or 1.3 tons. Add a 10–20% margin.

Does a dehumidifier heat up a grow room?

Yes. A dehumidifier adds all its electrical watts as heat (3.412 BTU/h per watt), and condensing water releases about 2,320 BTU of latent heat per litre (1,050 BTU/lb) back into the room as sensible heat. That heat isn't new: the plants took it from the room when they transpired the water. But your AC now has to remove it as sensible heat, so size the AC with the dehumidifier running.

How many tons of AC for a grow room?

One ton of cooling is 12,000 BTU/h (3.52 kW). Divide your total heat load in BTU/h by 12,000. A 4×4 ft tent with about 600 W of LED and fans plus a small dehumidifier adds about 2,600 BTU/h (0.2 ton); a sealed 10×10 ft room with about 3,300 W of LED is about 16,000 BTU/h (1.3 tons) before a 10–20% margin.

Is a portable air conditioner good for a grow room?

A single-hose portable air conditioner is a poor choice for a grow room. It blows room air outside to cool its condenser, which pulls the same amount of warm, unconditioned air back in through gaps, so its real cooling is lower than the label suggests. US energy rules now rate portable units with this infiltration counted. A dual-hose portable is better; a ductless mini-split is better still for a sealed room.

Should I oversize my grow room AC?

Only a little. A 10–20% margin covers hot days and growth, but a much larger unit cools the air quickly, shuts off, and removes less moisture, so humidity climbs. In a grow room that matters most in flower. A variable-speed (inverter) mini-split handles the swing between lights-on and lights-off better than an oversized single-speed unit.

Sources

  1. Thompson A, Taylor BN. 2008. NIST Special Publication 811, Appendix B (1 Btu_IT/h = 0.293 071 1 W; 1 ton of refrigeration = 12,000 Btu/h). National Institute of Standards and Technology. nist.gov/pml/special-publication-811
  2. ASHRAE. 2021. ASHRAE Handbook: Fundamentals, Chapter 18, Nonresidential Cooling and Heating Load Calculations (heat gain from lighting, equipment and occupants; occupant heat gain table). ashrae.org/technical-resources/ashrae-handbook
  3. NIST Chemistry WebBook. Water: enthalpy of vaporization (about 44 kJ/mol near 25 °C, about 2,440 kJ/kg). webbook.nist.gov/cgi/cbook.cgi?ID=C7732185
  4. US Department of Energy. Room air conditioners (sizing: an oversized unit cools quickly but removes less humidity). Energy Saver. energy.gov/energysaver/room-air-conditioners
  5. US Department of Energy. 2016 (1 June). Energy Conservation Program: Test Procedures for Portable Air Conditioners, final rule (Appendix CC, including infiltration air heat transfer for single-duct units and seasonally adjusted cooling capacity). Federal Register 81(105). govinfo.gov/content/pkg/FR-2016-06-01/html/2016-12446.htm
  6. US EPA. Section 608 Technician Certification (refrigerant handling for split systems). epa.gov/section608