Short answer, in plain words. Every part of a grow room depends on the part before it. Light decides the heat. Heat and water decide the cooling, the drying and the airflow. All of it decides the wiring. So work it out in order, write the numbers down, and measure once it's running. Each guide below gives the formulas in metric and imperial and worked examples for 2 × 4, 4 × 4, 5 × 5 and 4 × 8 ft tents and a 10 × 10 ft room. Supported.
Interactive versions: grow-room calculators, including a whole-tent planner.
The order to work in
- Light. PPFD target × canopy area ÷ 0.85 ÷ fixture µmol/J = wall watts. House recommendation: about 50 W/ft² of dimmable LED. → Lighting sizing
- Heat. Every watt of every device = 3.412 BTU/h [1][2]. → AC and cooling sizing
- Water. Plants transpire about what you water, minus runoff. → Dehumidifier sizing
- Air. Exhaust CFM for heat or one air change a minute, whichever is bigger; passive intakes 2–3× the duct area; a carbon filter rated for the real airflow. → Ventilation and carbon filters
- CO₂. Only for sealed, air-conditioned rooms with high light, and only with a monitor. → CO₂ calculations and safety
-
Power. Amps = watts ÷ volts; keep continuous loads to 80% of the breaker [3]. → Electrical load
-
Feed and water. Mix to an EC target, dilute with C₁V₁ = C₂V₂, size the reservoir for 3–5 days of water use. → Nutrient dilution and reservoir math (and EC vs PPM for the 500 and 700 scales)

LightPPFD × area ÷ 0.85 ÷ µmol/J- HeatEvery watt × 3.412 BTU/h
- WaterAbout what you water
- Air and coolingCFM or AC
- CO₂Sealed rooms only
- Power80% of the breaker
The five spaces at a glance
Flower, about 900 µmol/m²/s with a top-tier 3.0 µmol/J LED, 12/12, water use 4 L/m²/day; sealed-room CO₂ at 1,200 ppm. Rounded; every guide shows its assumptions.
| 2 × 4 tent | 4 × 4 tent | 5 × 5 tent | 4 × 8 tent | 10 × 10 room | |
|---|---|---|---|---|---|
| Canopy | 8 ft² (0.74 m²) | 16 ft² (1.49 m²) | 25 ft² (2.32 m²) | 32 ft² (2.97 m²) | 100 ft² (9.29 m²) |
| Volume | 48 ft³ | 104 ft³ | 163 ft³ | 208 ft³ | 800 ft³ |
| LED at 900 µmol/m²/s | ~260 W | ~525 W | ~820 W | ~1,050 W | ~3,280 W |
| House rec. 50 W/ft² (dimmable) | 400 W | 800 W | 1,250 W | 1,600 W | 5,000 W |
| Heat added (lights, fans, dehumidifier) | ~1,310 BTU/h | ~2,610 BTU/h | ~4,000 BTU/h | ~5,090 BTU/h | ~15,650 BTU/h (1.3 tons) |
| Water to remove | ~3 L (6 pt)/day | ~6 L (13 pt)/day | ~9 L (20 pt)/day | ~12 L (25 pt)/day | ~37 L (79 pt)/day |
| Exhaust CFM (heat, 10 °F rise) | ~95 | ~190 | ~290 | ~370 | ~1,130 (usually sealed + AC instead) |
| Passive intake (2–3× duct) | 4 in duct: 25–38 in² | 6 in duct: 57–85 in² | 6 in duct: 57–85 in² | 6–8 in duct: 57–150 in² | AC room: per design |
| CO₂ per 12 h day, sealed | ~0.09 lb | ~0.19 lb | ~0.29 lb | ~0.37 lb | ~1.2 lb |
| Amps at 120 V (lights, fans, dehumidifier) | ~5 A | ~8 A | ~11 A | ~13 A | ~36 A (or ~18 A at 240 V) |
Calculators vs articles
The articles explain why and show worked examples. A calculator is better when you're plugging in your own tent size, fixture efficacy, temperatures and water logs, or when one change should ripple through every other number (bigger lights → more heat → bigger fan, AC and circuits). That's what the whole-tent planner is for.